SKU:CDD4B100T13R
Greystone CDD4B100T13R Room, CO2, NDIR dual beam, c/w analog outputs, concealed LCD display, PT1000 Nickel RTD and relay
Greystone CDD4B100T13R Room, CO2, NDIR dual beam, c/w analog outputs, concealed LCD display, PT1000 Nickel RTD and relay
Couldn't load pickup availability
Greystone CDD4B100T13R is a room carbon dioxide (CO2) detector using dual-wavelength non-dispersive infrared (NDIR) sensing. It has a standard 0-20,000 ppm measurement range, with a programmable span from 2,000 to 20,000 ppm. CO2 accuracy is +/-75 ppm or 10% of reading, whichever is greater.
Configuration: concealed LCD; optional temperature sensor: 1,000 ohm nickel sensor, Class B, DIN 43760 with 2-wire resistive output; adjustable Form A normally open relay, rated 2 Amps at 140 Vac/30 Vdc; no optional override switch. The CO2 output is field-selectable as active 4-20 mA, 0-5 Vdc, or 0-10 Vdc. It operates on 20-28 Vac/dc and uses a white ABS IP30 (NEMA 1) enclosure for direct wall or single-gang electrical-box mounting.
Product Literature
- Datasheet — Greystone CDD4B1 Series Datasheet
Share