SKU:CDD4B100T2
Greystone CDD4B100T2 Room, CO2, NDIR dual beam, c/w analog outputs, concealed LCD display and PT100 ohm RTD
Greystone CDD4B100T2 Room, CO2, NDIR dual beam, c/w analog outputs, concealed LCD display and PT100 ohm RTD
Couldn't load pickup availability
Greystone CDD4B100T2 is a room carbon dioxide (CO2) detector using dual-wavelength non-dispersive infrared (NDIR) sensing. It has a standard 0-20,000 ppm measurement range, with a programmable span from 2,000 to 20,000 ppm. CO2 accuracy is +/-75 ppm or 10% of reading, whichever is greater.
Configuration: concealed LCD; optional temperature sensor: 100 ohm platinum RTD, IEC 751, 385 alpha, thin-film with 2-wire resistive output; no optional relay output; no optional override switch. The CO2 output is field-selectable as active 4-20 mA, 0-5 Vdc, or 0-10 Vdc. It operates on 20-28 Vac/dc and uses a white ABS IP30 (NEMA 1) enclosure for direct wall or single-gang electrical-box mounting.
Product Literature
- Datasheet — Greystone CDD4B1 Series Datasheet
Share