SKU:CMD5B5000-BAC
Greystone CMD5B5000-BAC Duct Carbon Monoxide Detector, BACnet communications, LCD and test switch
Greystone CMD5B5000-BAC Duct Carbon Monoxide Detector, BACnet communications, LCD and test switch
Couldn't load pickup availability
Greystone CMD5B5000-BAC is a duct-mounted carbon monoxide detector using an electrochemical sensor and a flow-through sample tube. The CO measurement range is menu selectable at 0-100, 0-150, 0-300, 0-400 or 0-500 ppm. Accuracy is +/-5 ppm or +/-5% of reading, whichever is greater, rated at 0-50 C.
The analog output is field selectable for active 4-20 mA, 0-5 Vdc or 0-10 Vdc. This model has no optional alarm relay and BACnet RS-485 communications.
A backlit LCD, status LED, front-panel test switch and alarm buzzer are standard. The test function can also be controlled through a remote digital input. On-board menu controls provide local configuration of the device parameters.
Power supply is 24 Vdc +/-20% or 24 Vac +/-10%. Operating conditions are -20 to 50 C (-4 to 122 F), 15-95% RH and 0.9-1.1 atm. Install through the side of the duct and secure using the mounting holes. Field calibration uses a calibration gas standard; follow the manufacturer installation instructions.
Product Features
- Measurement method: electrochemical sensor; diffusion or flow-through sampling for duct installations
- Measurement range: menu-selectable 100, 150, 300, 400, or 500 ppm carbon monoxide
- Accuracy: +/-5 ppm or +/-5% of reading, whichever is greater
- Output: active 4-20 mA or 0-5/0-10 Vdc; output type and scaling selected through the on-board menu
- Communications (suffix BAC): BACnet
- Relay option 000: no relay installed
- LCD: backlit display of ppm and menu parameters
- Test switch: front-panel I/O test; test can also be triggered by digital input
- Status LED: two-color red/green
- Buzzer: 85 dB at 10 cm; trip point programmable from 20 to 500 ppm in 10 ppm increments; delay 0 to 10 minutes
- Output resolution: 10-bit PWM (+/-0.4 ppm)
- Output drive at 24 Vdc: 450 ohm maximum for current; 10,000 ohm minimum for voltage
- Power supply: 24 Vdc +/-20% or 24 Vac +/-10%, non-isolated half-wave rectified; 100 mA maximum with all options on
- Operating conditions: -20 to 50 C (-4 to 122 F), 15 to 95% RH, 0.9 to 1.1 atm
- Stability: less than 5% signal loss per year; response time less than 35 seconds for a 90% step change
- Expected life: 5 to 7 years in air
- Enclosure: ABS, UL94-V0, IP65 (NEMA 4)
- Dimensions: 145 x 101 x 240 mm (5.7 x 4 x 9.4 in)
- Wiring: screw terminal block for 14 to 22 AWG
- Mounting: duct-mounted through the side of the duct
Product Literature
- Datasheet — Greystone CMD5B5 Series Datasheet
Share