SKU:CMD5B5110
Greystone CMD5B5110 Duct Carbon Monoxide Detector, two Form C relays, LCD and test switch
Greystone CMD5B5110 Duct Carbon Monoxide Detector, two Form C relays, LCD and test switch
Couldn't load pickup availability
Greystone CMD5B5110 is a duct-mounted carbon monoxide detector using an electrochemical sensor and a flow-through sample tube. The CO measurement range is menu selectable at 0-100, 0-150, 0-300, 0-400 or 0-500 ppm. Accuracy is +/-5 ppm or +/-5% of reading, whichever is greater, rated at 0-50 C.
The analog output is field selectable for active 4-20 mA, 0-5 Vdc or 0-10 Vdc. This model includes two Form C alarm relays; no optional network communications are included. Relay contacts provide normally open and normally closed connections, rated 5 A at 250 Vac or 30 Vdc. Relay trip points are programmable from 20-500 ppm in 10 ppm increments.
A backlit LCD, status LED, front-panel test switch and alarm buzzer are standard. The test function can also be controlled through a remote digital input. On-board menu controls provide local configuration of the device parameters.
Power supply is 24 Vdc +/-20% or 24 Vac +/-10%. Operating conditions are -20 to 50 C (-4 to 122 F), 15-95% RH and 0.9-1.1 atm. Install through the side of the duct and secure using the mounting holes. Field calibration uses a calibration gas standard; follow the manufacturer installation instructions.
Product Features
- Circuit board relay code 110: Two Form C relays
Product Literature
- Datasheet — Greystone CMD5B5 Series Datasheet
Share