SKU:SC-651-200
Greystone SC-651-200 AC Current Sensor, Split core sensor, 0 - 10 Vdc, 0 - 200 amp range
Greystone SC-651-200 AC Current Sensor, Split core sensor, 0 - 10 Vdc, 0 - 200 amp range
Couldn't load pickup availability
Greystone SC-651-200 is a self-powered split-core AC current sensor with a 0-10 Vdc output representing monitored load current. This model has a fixed 0-200 A measurement range. The maximum continuous input-current rating is 225 A, distinct from the calibrated measurement range.
The sensor is powered by induction from the monitored AC line and requires no external power supply. It operates at 50/60 Hz and uses a two-wire signal connection to the building automation system. Specified accuracy is +/-1% full-scale output over 5-100% of the selected measurement range. Typical response time is 200 ms for 0-90% response.
The typical output load is 1 megohm. The datasheet specifies an additional 0.5% loading error with a 100,000 ohm load. Screw terminals accept 14-22 AWG wiring. The sensing aperture is 20.3 mm (0.8 in), and specification-table dimensions are 76 x 79 x 24.9 mm (3.0 x 3.1 x 0.98 in).
The enclosure material is ABS/polycarbonate with a UL94-V0 material rating. Operating conditions are -15 to 60 C (5-140 F) and 5-90% RH, non-condensing. Install inside an electrical enclosure using the removable integral mounting tab for surface-screw mounting or spring mounting to a DIN rail. The sensor is for insulated conductors only, with a published 600 Vac insulation class. Follow the manufacturer installation instructions and applicable electrical safety procedures.
Typical applications include monitoring AC load current for pumps, conveyors, machine tools and fans. Current measurements can support motor-operation monitoring; this sensor provides an analog measurement signal, not the switched output of a current switch.
Product Literature
- Datasheet — Greystone SC-651 Series Datasheet
Share