SKU:SC-652-R1
Greystone SC-652-R1 AC Current Sensor, Split core sensor, 4 - 20 mA, (Average) 0 - 20 / 40 / 60 amp ranges, selectable
Greystone SC-652-R1 AC Current Sensor, Split core sensor, 4 - 20 mA, (Average) 0 - 20 / 40 / 60 amp ranges, selectable
Couldn't load pickup availability
Greystone SC-652-R1 is a split-core AC current sensor with a 4-20 mA output representing monitored load current. Its measurement ranges are 0-20 A, 0-40 A, 0-60 A, switch-selectable. The maximum continuous input-current rating is 100 A, distinct from the calibrated measurement range.
The sensor is loop-powered and requires a 15-30 Vdc supply. It operates at 50/60 Hz and uses a two-wire connection to the building automation system. Specified accuracy is +/-2% full-scale output over 5-100% of the selected measurement range. Typical response time is 250 ms for 0-90% response. The datasheet specifies a typical output load of 250 ohm.
Screw terminals accept 14-22 AWG wiring. The sensing aperture is 20.3 mm (0.8 in), and specification-table dimensions are 76 x 79 x 24.9 mm (3.0 x 3.1 x 0.98 in). The enclosure material is ABS/polycarbonate with a UL94-V0 material rating. Operating conditions are -15 to 60 C (5-140 F) and 5-90% RH, non-condensing.
Install inside an electrical enclosure using the removable integral mounting tab for surface-screw mounting or spring mounting to a DIN rail. The sensor is for insulated conductors only, with a published 600 Vac insulation class. Follow the manufacturer installation instructions and applicable electrical safety procedures.
Typical applications include monitoring AC load current for pumps, conveyors, machine tools and fans. Current measurements can support motor-operation monitoring; this sensor provides an analog measurement signal, not the switched output of a current switch.