Skip to product information
1 of 1

SKU:SC-675-R1

Greystone SC-675-R1 AC Current Sensor, Split core sensor, 4 - 20 mA, (True RMS) 0 - 10 / 20 / 50 amp ranges, selectable

Greystone SC-675-R1 AC Current Sensor, Split core sensor, 4 - 20 mA, (True RMS) 0 - 10 / 20 / 50 amp ranges, selectable

Regular price $113.92 USD
Regular price Sale price $113.92 USD
Sale
Shipping calculated at checkout.

Greystone SC-675-R1 is a split-core True RMS AC current sensor with a 4-20 mA output representing monitored load current. Its measurement ranges are 0-10 A, 0-20 A, 0-50 A, jumper-selectable. A precision RMS-to-DC converter supports measurement of complex, distorted or noisy waveforms, including VFD-controlled, phase-angle-controlled and time-proportional SCR-controlled loads.

The sensor is loop-powered and requires a 15-30 Vdc supply. It uses a two-wire connection to the building automation system and operates over 20-400 Hz. Specified accuracy is +/-2% full-scale output over 5-100% of the selected measurement range. Typical response time is 500 ms for 0-90% response, and the typical output load is 250 ohm. The manufacturer specifies a maximum continuous input-current rating of three times the selected range continuously, distinct from the calibrated measurement range.

Screw terminals accept 14-22 AWG wiring. The sensing aperture is 20.3 mm (0.8 in), and specification-table dimensions are 76 x 79 x 24.9 mm (3.0 x 3.1 x 0.98 in). The enclosure material is ABS/polycarbonate with a UL94-V0 material rating. Operating conditions are -15 to 50 C (5-122 F) and 5-90% RH, non-condensing.

Install inside an electrical enclosure using the removable integral mounting tab for surface-screw mounting or spring mounting to a DIN rail. The sensor is for insulated conductors only, with a published 600 Vac insulation class. Follow the manufacturer installation instructions and applicable electrical safety procedures.

Typical applications include AC current monitoring for pumps, conveyors, machine tools and fans. This model provides an analog current-measurement signal, not a switched alarm contact.

Product Literature

View full details