Greystone TE500H28D21A9H is a single-point rigid stack temperature transmitter for exhaust-stack and flue-gas temperature measurement. This model has a 200 mm (8 in) probe and a factory-configured 4-20 mA current-loop output scaled for 0-600 C.
The sensing element is a 1,000 ohm platinum RTD, three-wire, IEC 751, 385 alpha, wire-wound. Sensor accuracy is +/-0.3 C (+/-0.54 F) at 0 C (32 F). The 304 stainless-steel probe is 6.35 mm (0.25 in) in diameter, with a published probe temperature range of -100 to 600 C (-148 to 1112 F). This probe range is distinct from the configured 0-600 C transmitter output scale. Sensor wiring uses 22 AWG fiberglass-jacketed wire.
Transmitter accuracy is +/-0.1% of span, including linearity. The specified power input range for this output is 15-35 Vdc or 22-32 Vac. The transmitter includes reverse-voltage protection and an output-limited protection circuit. Follow the manufacturer installation and wiring instructions for the selected output; the three-wire RTD specification describes the sensing element, not a universal external transmitter wiring arrangement.
A cast-aluminum weatherproof enclosure rated IP64 (NEMA 3X) provides wiring connections through a screw terminal block accepting 14-22 AWG wiring. Transmitter ambient conditions are 0-70 C (32-158 F) and 0-95% RH, non-condensing, separate from the probe's high-temperature sensing range.
Install the probe through the side of the exhaust stack and secure the mounting flange directly to the stack wall. Select a probe length that places the tip close to the center of the stack, following the manufacturer installation instructions.
Product Features
- Sensor: 1000 ohm platinum RTD, 3-wire, IEC 751, 385 Alpha, wire wound
- Sensor accuracy: +/-0.3 C at 0 C
- Probe length: 200 mm (8 in)
- Probe temperature range: -100 to 600 C (-148 to 1112 F)
- Output signal: 4-20 mA current loop
- Transmitter scaled range: 0 to 600 C
- Probe: 304 series stainless steel, 6.35 mm (0.25 in) diameter
- Wire: 22 AWG fiberglass jacket
- Transmitter accuracy: +/-0.1% of span, including linearity
- Enclosure: cast aluminum, IP64 (NEMA 3X)
- Ambient conditions: 0 to 70 C (32 to 158 F), 0-95% RH non-condensing
Product Literature
- Datasheet — Greystone TE500H Series Datasheet