SKU:TSAPA07B
Greystone TSAPA07B Duct or Immersion Temperature Sensor
Greystone TSAPA07B Duct or Immersion Temperature Sensor
Couldn't load pickup availability
Greystone TSAPA07B is a single-point duct/immersion temperature sensor with a 10,000 ohm Type 3 NTC thermistor. Its rigid 304-series stainless-steel probe is 100 mm (4 in) long and 6 mm (0.236 in) in diameter. Specified thermistor accuracy is +/-0.2 C (+/-0.36 F) at 25 C (77 F). The sensor provides a passive resistance output, not an active current or voltage transmitter signal.
The A enclosure is ABS with a hinged and gasketed cover, rated IP65 (NEMA 4X). This configuration uses pigtail termination; follow the installation instructions for wiring. The probe sensing range is -40 to 100 C (-40 to 212 F). Ambient operating conditions are -40 to 60 C (-40 to 140 F) and 5-95% RH, non-condensing.
For duct applications, select a suitable probe length and install the probe in a straight section of duct at an appropriate distance downstream from heating, cooling, or humidification devices. This is a single-point sensor, not a duct-averaging sensor.
Immersion installation requires a suitable T2-series thermowell matched to the application and probe length. Use with a T1-series thermowell requires the T1AP-ADAPTER. Add thermal conductive compound inside the thermowell for optimum thermal transfer. Follow the manufacturer installation instructions for mounting and wiring.
Product Features
- Sensor (code 07): 10,000 ohm Type 3 NTC thermistor, +/-0.2 C
- Probe length (code B): 100 mm (4 in)
- Probe: 304 series stainless steel, 6 mm (0.236 in) diameter
- Probe sensing range: -40 to 100 C (-40 to 212 F)
- Ambient operating range: -40 to 60 C (-40 to 140 F), 5 to 95% RH non-condensing
- Enclosure (code A): hinged and gasketed ABS cover, UL94-V0, IP65 (NEMA 4X)
- Wire: 22 AWG PVC-insulated, parallel bonded
- For immersion use: install in the appropriate thermowell
Product Literature
- Datasheet — Greystone TSAP Series Datasheet