Senva CT1R-B3D-D Recessed Wall CO2 Sensor, LCD, Dual Channel, Temperature transmitter
Senva CT1R-B3D-D Recessed Wall CO2 Sensor, LCD, Dual Channel, Temperature transmitter
Couldn't load pickup availability
The Senva CT1R-B3D-D is a CT1R recessed-wall CO2 sensor with a dual-channel NDIR sensing element and an LCD display. A temperature transmitter is included. This option displays temperature on the LCD.
The 3-wire analog output supports 4-20 mA, 0-5 V, or 0-10 V. Default CO2 scaling is 0-2000 ppm. The LCD setup menu supports 0-2000, 0-5000, or 0-10000 ppm scaling. This display version includes a programmable normally open solid-state setpoint relay rated 1 A at 30 VAC/DC.
For the dual-channel CO2 element, specified accuracy is +/- (30 ppm + 3% of reading) at 0-2000 ppm and 0-50 degrees C; +/- (50 ppm + 3% of reading) at 2000-5000 ppm and -10 to 50 degrees C. Accuracy at 5000-10000 ppm is +/- (100 ppm + 10% of reading) at 0-50 degrees C. Supply requirements are 12-30 VDC, 50 mA maximum, or 24 VAC, 100 mA maximum. The 0-10 V output requires 15-30 VDC or 24 VAC. The enclosure is rated IP20/NEMA 1, with an overall operating range of -10 to 50 degrees C and 0-95% RH non-condensing.
Product Features
- Recessed Wall mounting
- Dual-channel NDIR CO2 element
- LCD display with setup menu
- Temperature transmitter
- Programmable N.O. relay: 1 A at 30 VAC/DC
- 3-wire 4-20 mA, 0-5 V, or 0-10 V analog output
- 0-2000 ppm default CO2 scaling
- 0-10 V output requires 15-30 VDC or 24 VAC
- IP20/NEMA 1 enclosure
- Temperature transmitter supports LCD temperature display
Product Literature
- Datasheet — Senva_CT1R_CT1W_Series_Datasheet