SKU:CT1R-F3X-D
Senva CT1R-F3X-D Recessed Wall CO2 Sensor, No LCD, Dual Channel, 10K ohm Type 3 thermistor
Senva CT1R-F3X-D Recessed Wall CO2 Sensor, No LCD, Dual Channel, 10K ohm Type 3 thermistor
Couldn't load pickup availability
The Senva CT1R-F3X-D is a CT1R recessed-wall CO2 sensor with a dual-channel NDIR sensing element and no LCD display. This configuration includes a 10K ohm Type 3 thermistor. The passive temperature option does not display temperature on the LCD.
The 3-wire analog output supports 4-20 mA, 0-5 V, or 0-10 V. Default CO2 scaling is 0-2000 ppm. This no-display version does not include the setpoint relay; LCD menu adjustment is not available.
For the dual-channel CO2 element, specified accuracy is +/- (30 ppm + 3% of reading) at 0-2000 ppm and 0-50 degrees C; +/- (50 ppm + 3% of reading) at 2000-5000 ppm and -10 to 50 degrees C. Supply requirements are 12-30 VDC, 50 mA maximum, or 24 VAC, 100 mA maximum. The 0-10 V output requires 15-30 VDC or 24 VAC. The enclosure is rated IP20/NEMA 1, with an overall operating range of -10 to 50 degrees C and 0-95% RH non-condensing.
Product Features
- Recessed Wall mounting
- Dual-channel NDIR CO2 element
- No LCD display
- 10K ohm Type 3 thermistor
- No setpoint relay
- 3-wire 4-20 mA, 0-5 V, or 0-10 V analog output
- 0-2000 ppm default CO2 scaling
- 0-10 V output requires 15-30 VDC or 24 VAC
- IP20/NEMA 1 enclosure
Product Literature
- Datasheet — Senva_CT1R_CT1W_Series_Datasheet
Share